+264 81 124 7788 info@itemengineering.com Box 1357, Oshakati, Erf 4736, Valombola, Ongwediwa, Namibia
 

HXP100DIP

HXP100DIP
HXP100DIP is a single phase two wire residential DIN-rail split prepayment meter, it complies with open standard (STS) and supported by Hexing/Itron /Landis+Gyr/Conlog...’s vending system. With a PLC communication, it can used for energy consumption monitoring and credit charging.
Supplier: Hexing

Specifications

application
Direct connection
accuracy
active
Class 1 or 2 (IEC), Class A or B (MID)
voltage
reference_voltage
110-127V, 220-240V
operating_voltage_range
70%-120%Un
current
basic_current
5A, 10A
maximum_current
60A, 80A, 100A
starting_current
<0.4%lb
frequency
50Hz or 60Hz
temperature
operation_range
-25°C~55°C
limit_range_for_storage_and_transport
-40°C~70°C
humidity
Up to 95% non-condensing
power_consumption
voltage_circuit_active
≤2 W
voltage_circuit_apparent
≤10 VA
current_circuit
≤1 VA
insulation_strength
ac_voltage_test
4kV during 1min
impulse_voltage_test
1.2/50µs mains connections 6kV
emc
electrostatic_discharges_contact
8kV
electrostatic_discharges_air
15kV
surge_immunity_test
4kV
fast_transient_burst_test
4kV
electromagnetic_rf_fields
10V/m(with current), 30V/m(without current)
connection_terminals
10mm
housing
protection_degree
IP51
meter_cover
Opaque PC+ glass fiber with a transparent window
meter_base
Opaque PC+ glass fiber
communication_interface
optical_communication
DLMS/COSEM
plc_alternative
HX645
weight
net_weight
Approx.0.31kg
package
Approx.0.08kg
dimension
138mmx83mmx48mm
standard
IEC62052-11, IEC62053-21, IEC62055-41, IEC62056-46, IEC62055-51, IEC62056-21, IEC62056-53, IEC62056-61, IEC62056-62, EN50470-1, EN50470-3